Technical Information
| Output Ratings |
| Voltage, Frequency |
Prime |
Standby |
| 400V, 50 Hz |
40 kVA / 32 kW |
44 kVA / 35,2 kW |
| Engine Technical Data |
| Make |
|
YANGDONG |
| Model |
|
Y4102D |
| No. of Cylinders |
|
4 |
| Cylinder Configuration |
|
In Line |
| Displacement |
lt |
3,88 |
| Bore |
mm |
100 |
| Stroke |
mm |
118 |
| Compression Ratio |
|
18 : 1 |
| Aspiration |
|
Natural |
| Governing Type |
|
Mechanic |
| Cooling Method |
|
Water |
| Cooling System Capacity |
lt |
17 |
| Total Oil Capacity |
lt |
11,4 |
| Engine Electrical System |
VDC |
12 |
| Speed / Frequency |
RPM / Hz. |
1500/50 |
| Gross Engine Power(Stand By 50 hz) |
kWm |
36 |
| Fuel Consumption 100 % 50 Hz |
lt/h |
8,3 |
| Fuel Consumption 75 % 50 Hz |
lt/h |
6,6 |
| Fuel Consumption 50 % 50 Hz |
lt/h |
5,1 |
| Alternator Technical Data |
| No of Phases |
|
3 |
| Power Factor |
|
0,8 |
| No of Bearings |
|
Single |
| No of Poles |
|
4 |
| No of Leads |
|
12/6 |
| Voltage Regulation (Steady State) |
|
± 1% |
| Insulation Class |
|
H |
| Protection Class |
|
IP 23 |
| Excitation System |
|
Self Excitation |
| Voltage regulator |
|
A.V.R. |
| Connection Type |
|
Star |
| Total Harmonic Content (No Load) |
|
<3% |
| Frequency |
|
50 |
| Voltage Output 50 Hz |
|
231/400 |
| Rated Power (Standby) 400V 50 Hz |
|
44 Kva |
Radio interference suppression that meets or exceeds EU standard EN61000-6. Voltage regulation at steady state.
Total Waveform distortion at full load.
*Powerpack reserves the right to change product specifications without notice.
Dimensions
| Dimensions |
W X L X H(mm) |
Weight(kg) |
Fuel Tank(lt) |
Sound Presure Level |
| dB(A)@7 mt |
| Canopied |
1000x2300x1350 |
825 |
115 |
73 |
| Open Skid |
1000x1750x1200 |
622 |
115 |
N/A |
Powerpack sound attenuated enclosures reduce sound levels to comply with the stage 2 levels of the European Community Directive 2000/14/EC
Height Excludes Exhaust Outlet, rain cap and any optional equipment on canopied models.
Optional Equipments
• Residential and Critical Silencers
• Remote radiator
• Automatic fuel filling system
• External Fuel Tank
• High Volume Base Fuel Tank
• Dual Wall Fuel Tank
• Fuel tank, oil pan, alternator, heaters
• Alternator with double AVR and PMG
• Synchronization systems
• The generator output breaker
• 3 Poles / 4 Poles Automatic Transfer Switch
• Super Silent Enclosure
• Trailer
• Remote monitoring