Technical Information
Output Ratings |
Voltage, Frequency |
Prime |
Standby |
400V, 50 Hz |
135 kVA / 108 kW |
150 kVA / 120 kW |
Engine Technical Data |
Make |
|
PERKINS |
Model |
|
1106A-70TG1 |
No. of Cylinders |
|
6 |
Cylinder Configuration |
|
In Line |
Displacement |
lt |
7,01 |
Bore |
mm |
105 |
Stroke |
mm |
135 |
Compression Ratio |
|
18,2 : 1 |
Aspiration |
|
Turbocharged & Intercooled |
Governing Type |
|
Electronic |
Cooling Method |
|
Water |
Cooling System Capacity |
lt |
21 |
Total Oil Capacity |
lt |
18 |
Engine Electrical System |
VDC |
12 |
Speed / Frequency |
RPM / Hz. |
1500/50 |
Gross Engine Power(Stand By 50 hz) |
kWm |
135,8 |
Fuel Consumption 100 % 50 Hz |
lt/h |
30,3 |
Fuel Consumption 75 % 50 Hz |
lt/h |
22,7 |
Fuel Consumption 50 % 50 Hz |
lt/h |
15,9 |
Alternator Technical Data |
No of Phases |
|
3 |
Power Factor |
|
0,8 |
No of Bearings |
|
Single |
No of Poles |
|
4 |
No of Leads |
|
12/6 |
Voltage Regulation (Steady State) |
|
± 1% |
Insulation Class |
|
H |
Protection Class |
|
IP 23 |
Excitation System |
|
Self Excitation |
Voltage regulator |
|
A.V.R. |
Connection Type |
|
Star |
Total Harmonic Content (No Load) |
|
<3% |
Frequency |
|
50 |
Voltage Output 50 Hz |
|
231/400 |
Rated Power (Standby) 400V 50 Hz |
|
150 Kva |
Radio interference suppression that meets or exceeds EU standard EN61000-6. Voltage regulation at steady state.
Total Waveform distortion at full load.
*Powerpack reserves the right to change product specifications without notice.
Dimensions
Dimensions |
W X L X H(mm) |
Weight(kg) |
Fuel Tank(lt) |
Sound Presure Level |
dB(A)@7 mt |
Canopied |
1050x3100x1725 |
1868 |
265 |
75 |
Open Skid |
1050x2400x1525 |
1531 |
265 |
N/A |
Powerpack sound attenuated enclosures reduce sound levels to comply with the stage 2 levels of the European Community Directive 2000/14/EC
Height Excludes Exhaust Outlet, rain cap and any optional equipment on canopied models.
Optional Equipments
• Residential and Critical Silencers
• Remote radiator
• Automatic fuel filling system
• External Fuel Tank
• High Volume Base Fuel Tank
• Dual Wall Fuel Tank
• Fuel tank, oil pan, alternator, heaters
• Alternator with double AVR and PMG
• Synchronization systems
• The generator output breaker
• 3 Poles / 4 Poles Automatic Transfer Switch
• Super Silent Enclosure
• Trailer
• Remote monitoring