Output Ratings | ||
Voltage, Frequency | Prime | Standby |
400V, 50 Hz | 23 kVA / 18,4 kW | 25 kVA / 20 kW |
Engine Technical Data | ||
Make | BAUDOUIN | |
Model | 4M06G4D0 | |
No. of Cylinders | 4 | |
Cylinder Configuration | In Line | |
Displacement | lt | 2,3 |
Bore | mm | 89 |
Stroke | mm | 92 |
Compression Ratio | 17 17,5 : 1 |
|
Aspiration | Natural | |
Governing Type | Electronic | |
Cooling Method | Water | |
Cooling System Capacity | lt | 9 |
Total Oil Capacity | lt | 11,5 |
Engine Electrical System | VDC | 12 |
Speed / Frequency | RPM / Hz. | 1500/50 |
Gross Engine Power(Stand By 50 hz) | kWm | 25 |
Fuel Consumption 100 % 50 Hz | lt/h | 6,1 |
Fuel Consumption 75 % 50 Hz | lt/h | 4,5 |
Fuel Consumption 50 % 50 Hz | lt/h | 3,2 |
Alternator Technical Data | ||
No of Phases | 3 | |
Power Factor | 0,8 | |
No of Bearings | Single | |
No of Poles | 4 | |
No of Leads | 12/6 | |
Voltage Regulation (Steady State) | ± 1% | |
Insulation Class | H | |
Protection Class | IP 23 | |
Excitation System | Self Excitation | |
Voltage regulator | A.V.R. | |
Connection Type | Star | |
Total Harmonic Content (No Load) | <3% | |
Frequency | 50 | |
Voltage Output 50 Hz | 231/400 | |
Rated Power (Standby) 400V 50 Hz | 25 Kva |
Radio interference suppression that meets or exceeds EU standard EN61000-6. Voltage regulation at steady state.
Total Waveform distortion at full load.
*Powerpack reserves the right to change product specifications without notice.
Dimensions | W X L X H(mm) | Weight(kg) | Fuel Tank(lt) | Sound Presure Level | |||
dB(A)@7 mt | |||||||
Canopied | 900x2000x1240 | 710 | 70 | 70 | |||
Open Skid | 900x1450x1143 | 536 | 70 | N/A |